Checking the Pressure Relief Valve in the Version 1 Cap
-- Position the Cooling System Tester:VAG1274B with the Adapter:VAG1274B/15 on the cap.
-- Generate approximately 2 bar (29.01 psi) pressure using the cooling system tester hand pump.
Blue Cap:
- The pressure must lower to 1.6 to 1.4 bar (23.21 to 20.31 psi) and stay there.
-- If the pressure relief valve does not react as specified, replace the cap.
Black Cap:
- The pressure must lower to 1.8 to 1.6 bar (26.11 to 23.21 psi) and stay there.
-- If the pressure relief valve does not react as specified, replace the cap.
Checking the Pressure Relief Valve in the Version 2 Cap:
-- Position the Cooling System Tester:VAG1274B with the Cooling System Tester - Adapter:VAG1274/9 on the cap.
-- Generate pressure with the cooling system tester hand pump.
Blue Cap:
- The pressure release valve must open at 1.4 to 1.6 bar (20.31 to 23.21 psi).
-- If the pressure relief valve does not react as specified, replace the cap.
Black Cap:
- The pressure release valve must open at 1.6 to 1.8 bar (23.21 to 26.11 psi).
-- If the pressure relief valve does not react as specified, replace the cap.
Additional procedures depending on the model: Refer to COOLING SYSTEM, CHECKING FOR LEAKS .