Possible Concerns

WARNING: This page is about a different car, the 2021 Audi S4 and 2021 Audi A4 Quattro. However, it is still accessible from the selected car via links, so may be relevant.
NOTE:

For all complaints marked *. Refer to PRESSURES, CHECKING  "Checking pressures".

If a malfunction occurs at only one evaporator in vehicles with two evaporators, also check the pressures in the refrigerant circuit.

Observe the test requirements. Refer to TEST REQUIREMENTS .

Vehicles without a High-Voltage System

Vehicles with a High-Voltage System

All Vehicles

From these, the following complaints may also occur:

The A/C Compressor Makes Noises

-- Tighten compressor securing bolts and compressor bracket using a torque wrench.

-- Check the routing of refrigerant lines; they must not touch other components and must not be subject to strain (align if necessary).

Noise (Refrigerant Hammer) Occurring Immediately after Switching on Air Conditioner and/or When Cornering or Braking

-- Discharge, evacuate and charge refrigerant circuit (too much refrigerant in circuit).

NOTE:

Too much refrigerant oil in the circuit could also cause this problem. This could occur if the amount of refrigerant oil was not adjusted when replacing the A/C compressor.

Water Sprays out of Vents (in Dash Panel or Footwell) Although Air Conditioning System is Otherwise Functioning Properly:

-- Check proper routing of condensate drain; it must not be crushed or kinked.

-- Check condensation drain valve, it must not be clogged by wax or underbody sealant and must close properly.

-- Check plenum chamber cover; it must not be damaged and must be properly installed (to stop water running into evaporator).

-- Check the water drains in plenum chamber; they must not be blocked (for example, by leaves).