Home >> Audi >> 2016 >> S5 Prestige, 2D Convertible >> Repair and Diagnosis >> External Pages >> Different car >> Section 39 (Heating & Air Conditioning) >> 87 Air conditioning >> A/C refrigerant system, testing >> Identifying malfunctions if specified values are not obtained >> Continuation of test - Pressure in refrigerant circuit increases

Continuation of test - Pressure in refrigerant circuit increases

WARNING: This page does not describe the selected car, but rather 17 other vehicles, including the 2009 Audi S4, 2009 Audi A4, 2008 Audi S4, 2008 Audi RS 4, and 2008 Audi A4. However, it is still accessible from the selected car via links, so may be relevant.
  • Operation of Coolant Fan V7 during cooling output test (speed is governed by coolant temperature and pressure in refrigerant circuit; determined by engine control unit)?
↓ Yes ↓ ↓ No ↓
  • Read measuring value block, display group "001" zone "4" (pressure in refrigerant circuit).
  • Operation of Coolant Fan V7 at higher speed with increase in pressure in refrigerant circuit (reading measuring value block, display group "014")
↓ Yes ↓ ↓ No ↓  
NOTE:
  • The pressure in the refrigerant circuit is governed by various factors. In general, however, at an ambient temperature of 20 to 25 °C the pressure should not exceed 20 bar. Under extreme usage conditions (e.g. in hot countries with high ambient temperatures, "stop and go traffic" and high relative humidity), the high cooling output then required may also result in pressures of up to 31 bar.
  • At ambient temperatures below 25 °C the pressure in the refrigerant circuit does not usually rise above 16 bar (Coolant Fan V7 run(s) and cool(s) condenser).
  • The duty cycle (reading measuring value block → Read Measuring Value Block (function 08) , display group "001", display zone "3") is used by the operating and display module, Climatronic Control Module J255 to calculate the pressure in the refrigerant circuit.
  • If the duty cycle is less than 12.5% (corresponding to approx. 1.8 bar absolute pressure) and greater than 87.5% (corresponding to approx. 32 bar absolute pressure), the operating and display module, Climatronic Control Module J255 does not switch on the compressor (the A/C Compressor Regulator Valve N280 is not activated). The compressor is only re-activated once the duty cycle exceeds 12.5% (corresponding to absolute pressure of 1.8 bar) or drops below 48% (corresponding to absolute pressure of 16 bar).
  • To prevent abrupt compressor shutoff because of excessive pressure in the refrigerant circuit or excessive coolant temperature, the compressor output is reduced by the operating and display module, Climatronic Control Module J255 :
  • - As soon as the pressure in the refrigerant circuit exceeds 30 bar (absolute) (full compressor output is not released again until pressure has dropped below 27 bar)
  • - As soon as the coolant temperature exceeds 115 °C (full shutdown at 118 °C)
  • If the pressure in the refrigerant circuit had been in excess of 32 bar (duty cycle greater than 87.5%), the operating and display module, Climatronic Control Module J255 does not reactivate the compressor until the pressure has dropped below 29 bar (duty cycle less than 84%).
  • For further notes on pressure in refrigerant circuit, refer to → Read Measuring Value Block (function 08) "Reading measuring value block", display group "001".