Engagement signal for A/C Compressor Regulator Valve N280, checking
WARNING: This page is about a different car, the 2008 Audi S4, 2008 Audi RS 4, and 2008 Audi A4. However, it is still accessible from the selected car via links, so may be relevant.
- Switch off ignition.
- Connect operating and display module, Climatronic Control Module J255 to vehicle wiring harness.
- Disconnect connector at air conditioner compressor (to A/C Compressor Regulator Valve N280).
Fig 1: Using Adapter From Connector Test Set V.A.G 1594C To Reestablish Connection Between Connector & Connector At Compressor
- Use adapter from Connector Test Set V.A.G 1594C to reestablish connection between connector - A - and connector - B - at compressor (to A/C Compressor Regulator Valve N280).
NOTE:
- Use can also be made for this test of an improvised adapter. This requires, for example, one connector - A - and - B - each (with part number 1J0 973 702 and 1J0 973 802 and the corresponding plug contacts), two commercially available sockets for banana plugs - C - and two wires with a cross section of 0.5 mm 2 .
- Connect Dso Measuring Leads 1 2 VAS 5051/8 to adapter leads.
- Measuring lead (signal wire) to contact 2
- Measuring wire (screen, Ground (GND)) to contact 1
- On Diagnostic Operation System VAS 5051A, set measurement mode: "DSO" (Digital Storage Oscilloscope).
- Settings 5V/div DC, 0.5 ms/div (5 V DC and 0.5 milliseconds per unit)
- Start engine.
- On operating and display module, Climatronic Control Module J255, select "Lo" temperature setting for drivers and front passengers side.
- On operating and display module, Climatronic Control Module J255, press buttons "Auto" and "ECON" to activate and deactivate A/C Compressor Regulator Valve N280.
Display on oscilloscope screen will be as follows depending on setting on operating and display module, Climatronic Control Module J255 :
- In "OFF" or "ECON" mode: no square-wave signal (A/C Compressor Regulator Valve N280 is not activated)
- In "Auto" mode and "Lo" temperature setting: Square-wave signal with pulse width - A - between 75% and 100% (A/C Compressor Regulator Valve N280 is activated)
NOTE:
- The illustration shows a signal with a ratio of approx. 80%.
- The pulse width - A - is governed by the required cooling output, electrical system voltage etc. (over width of area - A -, current is controlled via A/C Compressor Regulator Valve N280 by operating and display module, Climatronic Control Module J255).
- The signal distance - B - is always 2 milliseconds (corresponding to a frequency of 500 Hertz).
- The duty cycle is derived from the ratio of pulse width - A - to signal distance - B -.
- The setting on the operating and display module, Climatronic Control Module J255 and measured ambient influences govern the pulse width of the square-wave signal (signal ratio between 100% and greater than 30%, A/C Compressor Regulator Valve N280 is activated such that the compressor output required to obtain the specified temperatures is achieved).
NOTE:
- In "Auto" mode with "Lo" temperature setting, the A/C Compressor Regulator Valve N280 is activated such that the max. perm. current of approx. 0.6 to 0.8 A flows via the A/C Compressor Regulator Valve N280 (maximum compressor output).
- In control mode, the activation time is governed by the required cooling output and vehicle electrical system voltage, for example. It is however always of sufficient duration to achieve a mean current of 0.3 A.