Home >> Audi >> 2016 >> S5 Prestige, 2D Convertible >> Repair and Diagnosis >> External Pages >> Different car >> Section 1499 (Heating & Air Conditioning (On Board Diagnostic)) >> 01 On Board Diagnostic (OBD) >> Automatic Climate Control System, electrical testing >> Test steps "1" to "4" >> Test step "2"

Test step "2"

WARNING: This page is about a different car, the 2008 Audi S4, 2008 Audi RS 4, and 2008 Audi A4. However, it is still accessible from the selected car via links, so may be relevant.

Temperature sensors/sensors 

Diagnostic Operation System VAS 5051A, measurement mode: Multi-meter, resistance measurement (20kΩ/200 kΩ)
  • Adapter V.A.G 1598/11 connected
Test step Test Box V.A.G 1598A socket Test of
  • Test requirements 
  • Additional operations
Specified value Corrective actions for deviations from specification
2.1 30 + 34 Fresh Air Intake Duct Temperature Sensor G89
  • Ignition switched off
  • Measure temperature at sensor installation
  • Depending on temperature at sensor installation
  • Use wiring diagram to locate and eliminate short circuit, open circuit in wiring or contact resistance
2.2 31 + 34 Evaporator Vent Temperature Sensor G263    
  • Replace temperature sensor
2.3 28 + 34 Left Footwell Vent Temperature Sensor G261      
2.4 29 + 34 Right Footwell Vent Temperature Sensor G262      
Diagnostic Operation System VAS 5051A, measurement mode: Multi-meter, resistance measurement (20kΩ/200 kΩ)
  • Adapter V.A.G 1598/11 and Adapter - 16 Terminals V.A.G 1598/12 connected
Test step Test Box V.A.G 1598A socket Test of
  • Test requirements 
  • Additional operations
Specified value Corrective actions for deviations from specification
2.5 1 (1598/11) + 16 (1598/12) Left Vent Temperature Sensor G150
  • Ignition switched off
  • Measure temperature at sensor installation
  • Depending on temperature at sensor installation
  • Use wiring diagram to locate and eliminate short circuit, open circuit in wiring or contact resistance
2.6 2 (1598/11) + 16 (1598/12) Right Vent Temperature Sensor G151    
  • Replace sensor
NOTE:
  • The wiring to these sensors terminates at different connectors. Use is therefore either to be made of a second Test Box V.A.G 1598A or the measuring instrument must be connected using a suitable test lead from the Connector Test Set V.A.G 1594C directly to the Adapter - 16 Terminals V.A.G 1598/12.