Home >> Audi >> 2016 >> S5 Prestige, 2D Convertible >> Repair and Diagnosis >> External Pages >> Different car >> Section 1274 (General, Technical Data (Refrigerant R134A Servicing)) >> 00 General, Technical Data >> Refrigerant Circuit General Information >> Pressure Gauge, Tests And Measurements >> Pressure Gauge Uses

Pressure Gauge Uses

WARNING: This page is about a different car, the 2014 Volkswagen Touareg, 2013 Volkswagen Touareg, 2012 Volkswagen Touareg, and 2011 Volkswagen Touareg. However, it is still accessible from the selected car via links, so may be relevant.

A - Pressure And Temperature Measurement At Refrigerant Circuit 

NOTE:

The relationship between pressure and temperature indicated on the gauges only exists in a refrigerant circuit that contains liquid or vapor, but not gas. In a gaseous state, the temperature is approximately 10 °C (50 °F) to 30 °C (86 °F) higher than indicated on the gauge.

B - Verification of Refrigerant in a Closed Container 

Refrigerant R134a is present in a closed vessel or in a refrigerant circuit when the temperature indicator on the gauge matches the refrigerant temperature (the temperature of standing fluid is equal to the outside temperature).

A closed vessel or a refrigerant circuit that has been switched off is empty when the temperature indicated on the gauge is below the temperature of the refrigerant.

NOTE:

The relationship between pressure and temperature indicated on the gauges no longer applies if no liquid is present and the pressure is built up solely by gas.