Pressure Gauge Uses

WARNING: This page does not describe the selected car, but rather 9 other vehicles, including the 2018 Audi S6, 2018 Audi A6 Quattro, 2018 Audi A6, 2017 Audi S6, and 2017 Audi A6 Quattro. However, it is still accessible from the selected car via links, so may be relevant.

Pressure and Temperature Measurement at Refrigerant Circuit

NOTE:

The relationship between pressure and temperature indicated on the gauges only exists in a refrigerant circuit that contains liquid or vapor, but not gas. In a gaseous state, the temperature is approximately 10 to 30 °C (50 to 86 °F) higher than indicated on the gauge.

Verification of Refrigerant in a Closed Vessel

Refrigerant R1234yf is present in a closed vessel or in a refrigerant circuit when temperature indicator on the pressure gauge matches the refrigerant temperature (standing fluid adopts the ambient temperature).

A closed vessel or a refrigerant circuit which has been switched off is empty when temperature indication on the pressure gauge is below the temperature of the refrigerant.

NOTE:

The relationship between pressure and temperature indicated on the gauges no longer applies if no liquid is present and the pressure is built up solely by gas.

The pressure of the refrigerant R1234yf and R134a are very close over a very large temperature range, they cannot be differentiated by a pressure measurement. Distinguishing is possible for example using a gas analysis. Refer to REFRIGERANT R1234YF ANALYSIS .