Home >> Audi >> 2010 >> S4 Automatic DCT >> Repair and Diagnosis >> External Pages >> Different car >> Section 1046 (Climate Control System (General & Service Information)) >> 87 Air Conditioning >> Refrigerant Circuit General Information >> Pressure Gauge, Tests And Measurements >> Pressure Gauge Uses

Pressure Gauge Uses

WARNING: This page does not describe the selected car, but rather 9 other vehicles, including the 2018 Audi S6, 2018 Audi A6 Quattro, 2018 Audi A6, 2017 Audi S6, and 2017 Audi A6 Quattro. However, it is still accessible from the selected car via links, so may be relevant.

Pressure and Temperature Measurement at Refrigerant Circuit

NOTE:

The relationship between pressure and temperature indicated on the gauges only exists in a refrigerant circuit that contains liquid or vapor, but not gas. In a gaseous state, the temperature is approximately 10 °C to 30 °C (50 °F to 86 °F) higher than indicated on the gauge.

Verification of Refrigerant in a Closed Container

Refrigerant R134a is present in a closed container or in a refrigerant circuit when temperature indicator on the pressure gauge matches the refrigerant temperature (standing fluid adopts the ambient temperature).

A closed container or a refrigerant circuit which has been switched off is empty when temperature indication on the pressure gauge is below the temperature of the refrigerant.

NOTE:

The relationship between pressure and temperature indicated on the gauges no longer applies if no liquid is present and the pressure is built up solely by gas.