Warm Air Out Vents, Suction Line Is Cool To Warm, Discharge Line Is Warm To Hot, No Frost on Expansion Valve




Warm air comes out of the vents. The suction line is cool to warm, the discharge line is warm to hot, and there is no frost on the expansion valve

Probable cause: Excessive air and/or moisture in the system, indicating a possible leak

Do the refrigerant leak check A/C Refrigerant Leak Check and repair any leaks. Replace the receiver/dryer Service and Repair, then recharge the system to specifications A/C System Charging

Also check for

Climate control DTCs Initial Inspection and Diagnostic Overview

Also check for

Check the amount of refrigerant oil in the system. Adjust the oil level as needed.